This study investigates the performance of a refrigeration unit by applying a spray evaporative cooling system to an air-cooled chiller. Experiments are conducted in the temperate monsoon climate region by combining the spray evaporative cooling system with the air-cooled chiller. Moreover, this study adopts a new gas-liquid two-phase swirl nozzle, which is independently developed and characterized by high atomization quality and low energy consumption. The experimental results show that the power of the compressor is reduced, while the COP (Coefficient of Performance) of the air-cooled chiller increases by 4%-8% after the intervention of the spray evaporative cooling system. The spray cooling system contributes to an electricity savings of 2.37%-13.53% in air-cooled chiller systems. If a more reasonable spray evaporative cooling mode is used, such as controlling the water flows according to the cooling capacity and arranging the nozzle positions and angles reasonably, the COP of the air-cooled unit will be further improved.
Schlagwörter: 
Air-cooled chiller
Coefficient of performance
Evaporative cooling
Spray system
Persistent Identifier der Erstveröffentlichung: 
Creative-Commons-Lizenz: 
cc-by-nc-nd Logo
Dokumentart: 
Article
Erscheint in der Sammlung:

Datei(en):
Datei
Größe
2.56 MB





Publikationen in EconStor sind urheberrechtlich geschützt.